2005/07+2011+2015/16 – Axedale (Victoria) – E.coli, Trihalomethanes, Hardness, Aluminium, Total Dissolved Solids, Bromate

Axedale (Victoria) – E.coli
6/3/06: Axedale (Victoria) 36orgs/100mL. 98% compliance with no compliance during year.
There was a failure of the chlorinator at the Axedale Water Treatment Plant. The chlorinator was repaired immediately after notification of failure and an online chlorine analyser has since been installed at the plant to reduce the risk of failure reoccurring.
3/4/07: Axedale (Victoria) 1org/100mL.
No known cause – possibly due to low chlorine residual. Increased chlorine dosage rate to gain higher chlorine residual. Re-sampling completed showing no further E.Coli

30/8/11 Axedale E.coli  1/100mL

“E.coli

Thermotolerant coliforms are a sub-group of coliforms that are able to grow at 44.5 ± 0.2°C. E. coli is the most common thermotolerant coliform present in faeces and is regarded as the most specific indicator of recent faecal contamination because generally it is not capable of growth in the environment. In contrast, some other thermotolerant coliforms (including strains of Klebsiella, Citrobacter and Enterobacter) are able to grow in the environment and their presence is not necessarily related to faecal contamination. While tests for thermotolerant coliforms can be simpler than for E. coli, E. coli is considered a superior indicator for detecting faecal contamination…” ADWG

Axedale (Victoria) – Trihalomethanes

2005/06: Axedale (Victoria) – Trihalomethanes 250μg/L (maximum during year)

2006/07: Axedale (Victoria) – Trihalomethanes 390μg/L (maximum during year)

Trihalomethanes Australian Guideline Level 250μg/L

Why and how are THMs formed?
“When chlorine is added to water with organic material, such as algae, river weeds, and decaying leaves, THMs are formed. Residual chlorine molecules react with this harmless organic material to form a group of chlorinated chemical compounds, THMs. They are tasteless and odourless, but harmful and potentially toxic. The quantity of by-products formed is determined by several factors, such as the amount and type of organic material present in water, temperature, pH, chlorine dosage, contact time available for chlorine, and bromide concentration in the water. The organic matter in water mainly consists of a) humic substance, which is the organic portion of soil that remains after prolonged microbial decomposition formed by the decay of leaves, wood, and other vegetable matter; and b) fulvic acid, which is a water soluble substance of low molecular weight that is derived from humus”. US EPA

2005/06 – Axedale (Victoria) – Hardness

2005/06: Axedale (Victoria) Hardness 250mg/L (max), 207.5mg/L (mean)

2006/7: Axedale (Victoria) Hardness 280mg/L (max)

GUIDELINE

“To minimise undesirable build‑up of scale in hot water systems, total hardness (as calcium
carbonate) in drinking water should not exceed 200 mg/L.

Hard water requires more soap than soft water to obtain a lather. It can also cause scale to form on hot water pipes and fittings. Hardness is caused primarily by the presence of calcium and magnesium ions, although other cations such as strontium, iron, manganese and barium can also contribute.”

Axedale (Victoria) – Aluminium

2006/07: Axedale (Victoria) Aluminium 0.72mg/L (max)
Australian Guideline: Aluminium 0.2mg/L

According to the ADWG, no health guideline has been adopted for Aluminium, but that the issue is still open to review. Aluminium can come from natural geological sources or from the use of aluminium salts as coagulants in water treatment plants. According to the ADWG “A well-operated water filtration plant (even using aluminium as a flocculant) can achieve aluminium concentrations in the finished water of less than 0.1 mg/L.

The most common form of aluminium in water treatment plants is Aluminium Sulfate (Alum). Alum can be supplied as a bulk liquid or in granular form. It is used at water treatment plants as a coagulant to remove turbidity, microorganisms, organic matter and inorganic chemicals. If water is particularly dirty an Alum dose of as high as 500mg/L could occur. There is also concern that other metals may also exist in refined alum.

While the ADWG mentions that there is considerable evidence that Aluminium is neurotoxic and can pass the gut barrier to accumulate in the blood, leading to a condition called encephalopathy (dialysis dementia) and that Aluminium has been associated with Parkinsonism dementia and amyotrophic lateral sclerosis, the NHMRC, whilst also acknowledging studies which have linked Aluminium with Alzheimer disease, has not granted Aluminium a NOEL (No Observable Effect Level) due to insufficient and contradictory data. Without a NOEL, a health guideline cannot be established. The NHMRC has also stated that if new information comes to hand, a health guideline may be established in the future.

In communication with Aluminium expert Dr Chris Exley (Professor in Bioinorganic Chemistry
The Birchall Centre, Lennard-Jones Laboratories, Keele University, Staffordshire UK) in March 2013 regarding high levels of Aluminium detected in the South Western Victorian town of Hamilton
“It is my opinion that any value above 0.5 mg/L is totally unacceptable and a potential health risk. Where such values are maintained over days, weeks or even months, as indeed is indicated by the data you sent to me, these represent a significant health risk to all consumers. While consumers may not experience any short term health effects the result of longer term exposure to elevated levels of aluminium in potable waters may be a significant increase in the body burden of aluminium in these individuals. This artificially increased body burden will not return to ‘normal’ levels when the Al content of the potable water returns to normal but will act as a new platform level from which the Al body burden will continue to increase with age.

Axedale – Victoria – Total Dissolved Solids (Electrical Conductivity)

2006/07: Axedale (Victoria) – Total Dissolved Solids 1300EC (max)

GUIDELINE

“No specific health guideline value is provided for total dissolved solids (TDS), as there are no
health effects directly attributable to TDS. However for good palatability total dissolved solids
in drinking water should not exceed 600 mg/L.

Total dissolved solids (TDS) consist of inorganic salts and small amounts of organic matter that are dissolved in water. Clay particles, colloidal iron and manganese oxides and silica, fine enough to pass through a 0.45 micron filter membrane can also contribute to total dissolved solids.

Axedale (Victoria) – Bromate

2015/16 – Axedale (Victoria) – Bromate 0.02mg/L (maximum)

Bromate: Regulatory Standard = 0.02mg/L (Also see section of desalination). A suspected carcinogen. Bromate is formed when ozone used to disinfect drinking water reacts with naturally occurring bromide found in source water. Bromate formation in disinfected drinking water is influenced by factors such as bromide ion concentration, pH of the source water, the amount of ozone and the reaction time used to disinfect the water.