2007/8 + 2012/13 + 2018/19: Ararat (Victoria) – Trihalomethanes, Turbidity, Lead

Ararat (Victoria) – Trihalomethanes

2007/8 Ararat Trihalomethanes 0.340mg/L (Highest Level Only)

Trihalomethanes Australian Guideline Level 0.25mg/L

Why and how are THMs formed?
“When chlorine is added to water with organic material, such as algae, river weeds, and decaying leaves, THMs are formed. Residual chlorine molecules react with this harmless organic material to form a group of chlorinated chemical compounds, THMs. They are tasteless and odourless, but harmful and potentially toxic. The quantity of by-products formed is determined by several factors, such as the amount and type of organic material present in water, temperature, pH, chlorine dosage, contact time available for chlorine, and bromide concentration in the water. The organic matter in water mainly consists of a) humic substance, which is the organic portion of soil that remains after prolonged microbial decomposition formed by the decay of leaves, wood, and other vegetable matter; and b) fulvic acid, which is a water soluble substance of low molecular weight that is derived from humus”. Source: https://water.epa.gov/drink/contaminants/index.cfm

Ararat – Victoria – Turbidity

2012/13: Ararat (Victoria) – Turbidity 5.2 NTU (Maximum detection during year)

Chlorine-resistant pathogen reduction: Where filtration alone is used as the water treatment
process to address identified risks from Cryptosporidium and Giardia, it is essential
that filtration is optimised and consequently the target for the turbidity of water leaving
individual filters should be less than 0.2 NTU, and should not exceed 0.5 NTU at any time
Disinfection: A turbidity of less than 1 NTU is desirable at the time of disinfection with
chlorine unless a higher value can be validated in a specific context.

Aesthetic: Based on aesthetic considerations, the turbidity should not exceed 5 NTU at the
consumer’s tap.

Ararat (Victoria) Lead

2018/19 Ararat (Victoria) Lead 0.011mg/L.

Two compliance samples result were received from the laboratory with lead concentration of 0.11 mg/L in Ararat and the other at Murtoa. Investigation identified the root cause of the non-compliance as ‘sampling error, due to the use of disused taps at both locations that were not adequately flushed prior to sampling.

Lead Australian Drinking Water Guideline 0.01mg/L

“… Lead can be present in drinking water as a result of dissolution from natural sources, or from household plumbing systems containing lead. These may include lead in pipes, or in solder used to seal joints. The amount of lead dissolved will depend on a number of factors including pH, water hardness and the standing time of the water.

Lead is the most common of the heavy metals and is mined widely throughout the world. It is used in the production of lead acid batteries, solder, alloys, cable sheathing, paint pigments, rust inhibitors, ammunition, glazes and plastic stabilisers. The organo-lead compounds tetramethyl and tetraethyl lead are used extensively as anti-knock and lubricating compounds in gasoline…ADWG 2011