Doncaster – (Victoria) – E.coli
On 13 February 2008, an E. coli test result of 1 organism/100mL was reported from a sample taken from a customer tap in Doncaster. Extensive flushing of the mains in the affected area
was undertaken. E. coli was not detected in any of the subsequent additional samples collected across the locality.
Escherichia coli should not be detected in any 100 mL sample of drinking water. If detected
in drinking water, immediate action should be taken including investigation of potential
sources of faecal contamination.
“Coliforms are Gram-negative, non-spore-forming, rod-shaped bacteria that are capable of aerobic and facultative anaerobic growth in the presence of bile salts or other surface active agents with similar growth-inhibiting properties. They are found in large numbers in the faeces of humans and other warm-blooded animals, but many species also occur in the environment.
Thermotolerant coliforms are a sub-group of coliforms that are able to grow at 44.5 ± 0.2°C. E. coli is the most common thermotolerant coliform present in faeces and is regarded as the most specific indicator of recent faecal contamination because generally it is not capable of growth in the environment. In contrast, some other thermotolerant coliforms (including strains of Klebsiella, Citrobacter and Enterobacter) are able to grow in the environment and their presence is not necessarily related to faecal contamination. While tests for thermotolerant coliforms can be simpler than for E. coli, E. coli is considered a superior indicator for detecting faecal contamination…” ADWG 2011
Doncaster (Victoria) – Lead
2024/25: Doncaster Lead 0.0046mg/L (max), 0.0015mg/L (av.)
Lead Guideline reduced from 0.01mg/L to 0.005mg/L in June 2025. “The concentration of lead in water within premises may be higher, especially in older buildings, due to contact of the water with lead-containing plumbing products (enHealth 2021). A review found several Australian and international studies that detected up to 0.162 mg/L of lead in drinking water due to leaching from lead-containing plumbing materials including taps and lead service lines, suggesting that leaching of lead from lead-containing plumbing materials can be substantial (SLR 2023)… Based on health considerations, the concentration of lead in drinking water should not exceed 0.005 mg/L