2010/11 + 2022/23: Murchison (Victoria) – Manganese, Turbidity, Chloral Hydrate

2022/23: Murchison (Victoria) Manganese

2022/23: Murchison (Victoria) Manganese 0.82mg/L (max)

Manganese: ADWG Guidelines 0.5mg/L. ADWG Aesthetic Guideline 0.1mg/L
Manganese is found in the natural environment. Manganese in drinking water above 0.1mg/L can give water an unpleasant taste and stain plumbing fixtures and laundry.

Murchison (Victoria)  Turbidity

2022/2023: Murchison (Victoria) 4.9 (max), 0.4 (maximum 95th percentile)

Chlorine-resistant pathogen reduction: Where filtration alone is used as the water treatment
process to address identified risks from Cryptosporidium and Giardia, it is essential
that filtration is optimised and consequently the target for the turbidity of water leaving
individual filters should be less than 0.2 NTU, and should not exceed 0.5 NTU at any time
Disinfection: A turbidity of less than 1 NTU is desirable at the time of disinfection with
chlorine unless a higher value can be validated in a specific context.
Aesthetic: Based on aesthetic considerations, the turbidity should not exceed 5 NTU at the
consumer’s tap.

Murchison (Victoria)

Highest Detections only  2010/11

Murchison 23ug/L Chloral Hydrate 2010/11

2004 Australian Drinking Water Guideline: Trichloroacetaldehyde (chloral hydrate): 0.02mg/L

2011 Australian Drinking Water Guideline: Trichloroacetaldehyde (chloral hydrate): 0.1mg/L

“Chloral hydrate is a disinfection by-product, arising from chlorination of water containing naturally occurring organic material (NOM). Chloral hydrate has only been detected by Goulburn Valley Water since changing to a new contract testing laboratory in November 2007. The Department of Health is currently conducting a study into the detection of chloral hydrate across Victoria.”