2011 February: Centenary Reservoir Maryborough (Victoria) – Microcystis

Centenary Reservoir Offtake (Maryborough)

15 February 2011 (37 days): Microcystis sp. – 2.29mm3/L biovolume. Increased monitoring regime in accordance with BGA Management Plan. Reservoir isolated from supply and carbon dosing initiated at treatment plant. Reservoir spot dosed with algaecide and toxicity testing undertaken. Informed DH of initial and subsequent test results. (CHW Annual Drinking Water Quality Report 2010/11)