2012/17 + 2022: Rowena (NSW) – E.coli, Chloride, Lead, Sodium, Total Dissolved Solids

Rowena (NSW) – E.coli

16/2/22: Public Notice Rowena Water Supply. Walgett Shire Council wishes to advise the residents of Rowena that E.coli has been detected in a recent water sample, therefore all residents are asked to boil their tap water before drinking. Council staff are working to identify the problem and the reservoir will be super chlorinated today. Flushing of the mains around the village will be flushed for the next couple of days…

2012-17: Rowena (NSW) – E.coli 3mpn/100mL (max), (0.1) average

Escherichia coli should not be detected in any 100 mL sample of drinking water. If detected
in drinking water, immediate action should be taken including investigation of potential
sources of faecal contamination.

“Coliforms are Gram-negative, non-spore-forming, rod-shaped bacteria that are capable of aerobic and facultative anaerobic growth in the presence of bile salts or other surface active agents with similar growth-inhibiting properties. They are found in large numbers in the faeces of humans and other warm-blooded animals, but many species also occur in the environment.

Thermotolerant coliforms are a sub-group of coliforms that are able to grow at 44.5 ± 0.2°C. E. coli is the most common thermotolerant coliform present in faeces and is regarded as the most specific indicator of recent faecal contamination because generally it is not capable of growth in the environment. In contrast, some other thermotolerant coliforms (including strains of Klebsiella, Citrobacter and Enterobacter) are able to grow in the environment and their presence is not necessarily related to faecal contamination. While tests for thermotolerant coliforms can be simpler than for E. coli, E. coli is considered a superior indicator for detecting faecal contamination…” ADWG 2011

Rowena (NSW) Lead

2012/17 – Rowena (NSW) – Lead 0.01mg/L (max)

Lead Australian Drinking Water Guideline 0.01mg/L

“… Lead can be present in drinking water as a result of dissolution from natural sources, or from household plumbing systems containing lead. These may include lead in pipes, or in solder used to seal joints. The amount of lead dissolved will depend on a number of factors including pH, water hardness and the standing time of the water.

Lead is the most common of the heavy metals and is mined widely throughout the world. It is used in the production of lead acid batteries, solder, alloys, cable sheathing, paint pigments, rust inhibitors, ammunition, glazes and plastic stabilisers. The organo-lead compounds tetramethyl and tetraethyl lead are used extensively as anti-knock and lubricating compounds in gasoline…ADWG 2011

2012/17: Rowena (NSW) – Sodium

2012/17: Rowena Sodium 238mg/L (max), 219 mg/L (average)

“Based on aesthetic considerations (taste), the concentration of sodium in drinking water
should not exceed 180 mg/L….The sodium ion is widespread in water due to the high solubility of sodium salts and the abundance of mineral deposits. Near coastal areas, windborne sea spray can make an important contribution either by fallout onto land surfaces where it can drain to drinking water sources, or from washout by rain. Apart from saline intrusion and natural contamination, water treatment chemicals, domestic water softeners and
sewage effluent can contribute to the sodium content of drinking water.” ADWG 2011

 

Rowena  (NSW) – Total Dissolved Solids

2012/17: Rowena Total Dissolved Solids 630mg/L (max), 567mg/L (average)

GUIDELINE

“No specific health guideline value is provided for total dissolved solids (TDS), as there are no
health effects directly attributable to TDS. However for good palatability total dissolved solids
in drinking water should not exceed 600 mg/L.

Total dissolved solids (TDS) consist of inorganic salts and small amounts of organic matter that are dissolved in water. Clay particles, colloidal iron and manganese oxides and silica, fine enough to pass through a 0.45 micron filter membrane can also contribute to total dissolved solids.

Total dissolved solids comprise: sodium, potassium, calcium, magnesium, chloride, sulfate, bicarbonate, carbonate, silica, organic matter, fluoride, iron, manganese, nitrate, nitrite and phosphates…” Australian Drinking Water Guidelines 2011

Rowena (NSW) – Chloride

2012/17: Rowena Chloride 257mg/L (max), 195mg/L (average)

“Chloride is present in natural waters from the dissolution of salt deposits, and contamination from effluent disposal. Sodium chloride is widely used in the production of industrial chemicals such as caustic soda, chlorine, and sodium chlorite and hypochlorite. Potassium chloride is used in the production of fertilisers.

The taste threshold of chloride in water is dependent on the associated cation but is in the range 200–300 mg/L. The chloride content of water can affect corrosion of pipes and fittings. It can also affect the solubility of metal ions.

In surface water, the concentration of chloride is usually less than 100 mg/L and frequently below 10 mg/L. Groundwater can have higher concentrations, particularly if there is salt water intrusion.

Based on aesthetic considerations, the chloride concentration in drinking water should not exceed 250 mg/L.

No health-based guideline value is proposed for chloride.” 2011 Australian Drinking Water Guidelines