Based on health considerations, the guideline value for total chlorine in drinking water is 5 mg/L.
GENERAL DESCRIPTION
Chlorine dissociates in water to form free chlorine, which consists of aqueous molecular chlorine, hypochlorous acid and hypochlorite ion. Chlorine and hypochlorites are toxic to microorganisms and are used extensively as disinfectants for drinking water supplies. Chlorine is also used to disinfect sewage and wastewater, swimming pool water, in-plant supplies, and industrial cooling water.
Chlorine has an odour threshold in drinking water of about 0.6 mg/L, but some people are particularly sensitive and can detect amounts as low as 0.2 mg/L. Water authorities may need to exceed the odour threshold value of 0.6 mg/L in order to maintain an effective disinfectant residual.
In the food industry, chlorine and hypochlorites are used for general sanitation and for odour control. Large amounts of chlorine are used in the production of industrial and domestic disinfectants and bleaches, and it is used in the synthesis of a large range of chemical compounds.
Free chlorine reacts with ammonia and certain nitrogen compounds to form combined chlorine. With ammonia, chlorine forms chloramines (monochloramine, dichloramine and nitrogen trichloride or trichloramine) (APHA 2012). Chloramines are used for disinfection but are weaker oxidising agents than free chlorine.
Free chlorine and combined chlorine may be present simultaneously (APHA 2012). The term totalchlorine refers to the sum of free chlorine and combined chlorine present in a sample.
Chlorine (Free) ADWG Guideline: 5mg/L (Chlorine in chloraminated supplies 4.1mg/L). Chlorine dissociates in water to form free chlorine, which consists of aqueous molecular chlorine, hypochlorous acid and hypochlorite ion.
Chlorine (Total) ADWG Guideline 5mg/L (chloraminated supplies 4.1mg/L): The term total chlorine refers to the sum of free chlorine and combined chlorine present in a sample
Dysart (Queensland) – Lead
2018/19: Dysart Lead 0.00402mg/L (max), 0.001308mg/L (av.)
Lead Guideline reduced from 0.01mg/L to 0.005mg/L in June 2025. “The concentration of lead in water within premises may be higher, especially in older buildings, due to contact of the water with lead-containing plumbing products (enHealth 2021). A review found several Australian and international studies that detected up to 0.162 mg/L of lead in drinking water due to leaching from lead-containing plumbing materials including taps and lead service lines, suggesting that leaching of lead from lead-containing plumbing materials can be substantial (SLR 2023)… Based on health considerations, the concentration of lead in drinking water should not exceed 0.005 mg/L.”
Dysart (Queensland) – Turbidity
2016/17: Dysart (Queensland) – Turbidity 92 NTU (Maximum detection during year), 7.54NTU av.
Chlorine-resistant pathogen reduction: Where filtration alone is used as the water treatment
process to address identified risks from Cryptosporidium and Giardia, it is essential
that filtration is optimised and consequently the target for the turbidity of water leaving
individual filters should be less than 0.2 NTU, and should not exceed 0.5 NTU at any time
Disinfection: A turbidity of less than 1 NTU is desirable at the time of disinfection with
chlorine unless a higher value can be validated in a specific context.
Aesthetic: Based on aesthetic considerations, the turbidity should not exceed 5 NTU at the
consumer’s tap
Dysart (Queensland) – Manganese
2014/15: Dysart (Queensland) – Manganese 1.7mg/L (maximum). 0.096mg/L (average)
7 samples exceeded guidelines
Manganese: ADWG Guidelines 0.5mg/L. ADWG Aesthetic Guideline 0.1mg/L
Manganese is found in the natural environment. Manganese in drinking water above 0.1mg/L can give water an unpleasant taste and stain plumbing fixtures and laundry.